• 矿用电缆(2).jpg

MYJV Mining cable

Brand:

MINGDA

Type:

MYJV Series

Material:

Copper

Description

XLPE insulated power cable for coal mine

First, product standards

This product is produced according to MT818-2009 "Flame-retardant Cable for Coal Mine" and related enterprise standards, 

II. Scope of application

This product is suitable for fixed installation in distribution networks or industrial installations with a rated power frequency of 10 kV and below.

III. Working temperature and laying conditions

a) The allowable long-term maximum temperature of the cable conductor does not exceed 90℃.

b) The maximum temperature of the cable conductor does not exceed 250℃ during short circuit (the longest time does not exceed 5S).

*laying on the ground

d) The ambient temperature shall not be lower than 0℃ when the cable is laid.

e)The cable bending radius is:

Single core cable: 20(D+d)±5%

Three-conductor cable: 15(D+d)±5%

Four. Cable model

Model Name Applicability
MYJV Coal mine copper core XLPE insulated PVC sheathed power cable Indoor tunnels and cable trenches cannot withstand mechanical external forces.
MYJV22 Coal mine copper core XLPE insulated steel tape armored PVC sheathed power cable
MYJV32 Coal mine copper core XLPE insulated fine steel wire armored PVC sheathed power cable Indoors, tunnels, cable trenches or directly buried underground, it can be used in humid environments and places with high groundwater levels, and can withstand certain mechanical external forces and certain tensile forces.
MYJV42 Coal mine copper core XLPE insulated thick steel wire armored PVC sheathed power cable

V. Production Scope

Model Number of cores Rated Voltage (kV)
0.6/1 1.8/3 3.6/6 6/10, 8.7/10
Nominal Section
MYJV 3 1.5-300 10-300 25-300 25-300
MYJV22 3 4-300 10-300 25-300 25-300
MYJV32 3 4-300 10-300 25-300 25-300
MYJV42 3 4-300 10-300 25-300 25-300

6. Voltage test

1. The voltage test should be carried out at ambient temperature, and the manufacturer can choose to use power frequency AC voltage or DC voltage.

2. Test voltage

0.6/1 kV power frequency test voltage is 2.5U0+2kV, and the single-phase test voltage corresponding to the standard rated voltage is as follows:

rated voltage U0kV 0.6 1.8
Test voltage kV 3.5 6.5
time min 5 5

(1) If a three-phase transformer is used to conduct a voltage test on a three-core cable at the same time, the phase-to-phase test voltage should be 1.73 times the data listed in the table above.

(2) When the DC voltage is used for the voltage test, the DC voltage value should be 2.4 times the power frequency AC voltage value.

(3) In any case, the voltage should be gradually raised to the specified value.

(4) Voltage test, partial discharge test

1. The test voltage should be carried out on the coiled cable. When a voltage of 1.5U0 is applied, the discharge of the PVC insulated cable should not be greater than 40pC. The discharge amount of XLPE insulated cables with rated voltage U0 of 8.7 kV and below is not more than 20 pC.

2. Test voltage

The power frequency test voltage of 3.6/6kV and above is 2.5U0, and the single-phase test voltage corresponding to the standard rated voltage is as follows:

rated voltage U0kV 3.6/6 6/6, 6/10 8.7/10
Test voltage kV 11 15 22
time min 5 5

More products


图片名称

Name

Serial number

Brand

Material

MORE

BVVB Wire

National stan 2*0.75~6;3*0.75~6

MINGDA

Oxygen free copper

RVS Wre

National standard rvs2 * 0.5 ~ 6

MINGDA

Oxygen free copper

RVV Line

National standard rvv2 core 3-co

MINGDA

Oxygen free copper

BV Wire

National standard BV-1.5~16

MINGDA

Oxygen free copper

MVV Mining cable

MVV Series

MINGDA

Copper

MYJV Mining cable

MYJV Series

MINGDA

Copper

NH-VV Fire resistant cable

NH-VV Series

MINGDA

Copper

YZ Rubber sheathed cable

YZ Series

MINGDA

Copper

Bbtrz insulated copper core flexible mineral insulated fireproof cable

BBTRZ

MINGDA

Copper

NG-A(BTLY) Copper core aluminum metal sheathed polyolefin sheathed isolated flexible mineral insulated fireproof cable

BTLY Series

MINGDA

Copper core